Configuration and function of the modules english – Burkert Type 8645 User Manual

Page 73

Advertising
background image

ConfiGuraTion anD funCTion of The moDules

English

8645 - 7

Object

class

Instance

Attri-

butes

Ac-

cess

Length

byte

Area

Default Short Description

Report
outputs

150

1



Get/

Set

1

0 or 1

0

Turn on/off output
reports (short circuit
or non-present OUT)
0: Activate output
reports
1 : Deactivate output
reports

Filter inputs

150

1

4

Get/

Set

1

0 or 1

0

Input filter
1: Filter OFF
0: Filter ON

Write
EEPROM

150

1

5

Set

1

1 to 

Data can be written
into EEPROM with
this object.

1: Actual module list
is written in EEPROM.
After power-up, it
becomes the Target
module list.

2: As valuje 1, but
here, at the end, a
Diag Byte with the
generated data will be
sent.

: Object Error action,
value, filter input and
reports output are
written into EEPROM.

Diagnose
Error type
and number

151

1

1

Get

1

Error type (MSB 4
Bit) and error number
(LSB 4 Bit) as per
LED display, Byte can
be transferred
cyclically.

Short-circuit
channel,
bus head

151

1

2

Get

1

1 diagnosis bit per 2
bus head outlets.

RIO/ZM

151

1



Get

1

Diagnosis of a RIO/
ZM,
address of a RIO or
ZM, which has a Diag;
MSB shows whether
ZM (0) or RIO (1)

Channel
short circuit
RIO/ZM

151

1

4

Get

1

1 diagnosis bit per 2
RIO/ZM outlets

The effected RIO/ZM
module is shown in
object 151/1/.

Discrete Output
Value

9

1 to 16



Get/

Set

2

0x0000

to

0xFFFF

0x0000 Valve value

Advertising