Commissioning english – Burkert Type 8645 User Manual

Page 129

Advertising
background image

CommissioninG

English

8645 - 129

The following mask appears:

Illustration: Parameterisation of the slave - object properties 

Explanation of the device-specific paramters

parameters

Explanation

Data Exchange Mode
Without Global Control-Operate

Activate / deactivate Global Control Operate

On Global Control-Operate only

In order to enter Data Exchange mode, the master must transmit a Glo-
bal Control Operate. Otherwise, the BUS (BF) LED flashes
(e. g.if the PLC is at stop).

Short circuit detection

Short circuit detection

With Short circuit detection

Short circuits on the digital outputs and non-existent driven outputs are
detected. Incorrect messages can be output, however, in the event of
capacitive loads.

Without Short circuit detection

Short circuits on the digital outputs and non-existent driven outputs are
not detected.

Input filter

Input filter

Input filter ON

Only signals with a length >4 ms are detected on the feedback inputs.
Incorrect messages due to ESD are thus avoided.

Input filter OFF

Signals with a length of <4 ms are also detected on the feedback in-
puts. Incorrect messages may therefore be transmitted when using M8
plugs (without plastic insert) due to ESD.