4 hardware installation, 1 supervisor board installation, 1 mechanical specification – Micromod Micro-PWC: 53PW6000 MicroPWC Installation and Setup Manual User Manual

Page 27: 2 electrical specification, 3 environmental specification, 4 jumper settings, Section 3.4.1

Advertising
background image

Micro-PWC

Installation & Setup Guide

Installation 17

3.4 Hardware Installation

3.4.1 Supervisor Board Installation

The Supervisor board for the ISA bus is an optional Micro-DCI network communication printed circuit
board. The Supervisor board provides the software products running on PC with the ability to communi-
cate with the Micro-DCI Networks. (If your Micro-PWC system is not equipped with Supervisor boards, you
may skip to

Section 3.4.2

.)

3.4.1.1 Mechanical Specification

The Supervisor board is a rectangular board measuring 12.3 inches by 3.9 inches.

3.4.1.2 Electrical Specification

Power Requirements:

3.4.1.3 Environmental Specification

Temperature: 0 to +60 degrees C (board only)

The temperature specification of the personal computer is a function of other product component tempera-
ture specifications (if lower) and internal temperature gradients.

3.4.1.4 Jumper Settings

The Supervisor board has three jumpers (J3, J4 and J5) that set the I/O-Port address for the board. These
are set at the factory for I/O address 300H.

Figure 3-3

shows the jumper settings that provide alternate

addressing if required, possibly for multiple board installations. Using the board's jumpers, select a unique
I/O address for each Supervisor Board in the system based on the results of activities performed for

Section 3.3, Determine I/O Address for Supervisor Board

.

To change the I/O address set by these three jumpers, remove the plastic "shorting block" from the two
undesired jumper pins and slide it over the pins that create the desired I/O address for this supervisor
board. You can change the settings on one, two, or all three jumpers.

NOTE

One full-size ISA bus slot must be available for each Supervisor
board installed in the personal computer on which the Micro-PWC
system software will be used. An additional half-size ISA bus slot is
required immediately to the right of each Microlink Supervisor board
for which a redundant network connection is required.

Component

Requirement

Voltage

5 V dc =/- 5%

Current

1.5 Amps