Overview – Agilent Technologies N5183A MXG User Manual

Page 148

Advertising
background image

138

Agilent N518xA, E8663B, E44x8C, and E82x7D Signal Generators Programming Guide

Programming the Status Register System
Overview

Overview

NOTE

Some of the status bits and register groups only apply to select signal generators with
certain options. For more specific information on each exception, refer to the following:

Standard Operation Condition Register bits (see

Table 4- 5 on page 160

)

Baseband Operation Status Group (see

page 162

)

Data Questionable Condition Register bits (see

Table 4- 7 on page 166

)

Data Questionable Power Condition Register bits (see

Table 4- 8 on page 169

)

Data Questionable Frequency Condition Register bits (see

Table 4- 9 on page 172

)

Data Questionable Modulation Condition Register bits (see

Table 4- 10 on page 175

)

Data Questionable Calibration Condition Register bit (see

Table 4- 11 on page 178

)

Data Questionable Bert Status Group (see

page 180

)

During remote operation, you may need to monitor the status of the signal generator for error
conditions or status changes. You can use the signal generator’s status register system to monitor
error conditions, or condition changes, or both. In general, the error queue is easier to use than the
status registers, but the status registers provide some additional information not found in the error
queue. For more information on using the signal generator’s SCPI commands to query the signal
generator’s error queue, refer to signal generator’s SCPI command reference guide, to see if any
errors have occurred.

The signal generator’s status register system provides two major advantages:

You can monitor the settling of the signal generator using the settling bit of the Standard
Operation Status Group’s condition register.

You can use the service request (SRQ) interrupt technique to avoid status polling, therefore giving
a speed advantage.

The signal generator’s instrument status system provides complete SCPI compliant data structures for
reporting instrument status using the register model.

The SCPI register model of the status system has multiple registers that are arranged in a
hierarchical order. The lower- priority status registers propagate their data to the higher- priority
registers using summary bits. The Status Byte Register is at the top of the hierarchy and contains the
status information for lower level registers. The lower level registers monitor specific events or
conditions.

The lower level status registers are grouped according to their functionality. For example, the Data
Questionable Frequency Status Group consists of five registers. This chapter may refer to a group as
a register so that the cumbersome longer description is avoided. For example, the Standard Operation
Status Group’s Condition Register can be referred to as the Standard Operation Status register. Refer
to

“Status Groups” on page 156

for more information.

Figure 4- 1

,

Figure 4- 2

,

Figure 4- 3

,

Figure 4- 4

,

Figure 4- 5

,

Figure 4- 6

,

Figure 4- 7

, and

Figure 4- 8

shows each signal generator model’s status byte register system and hierarchy.

The status register systems use IEEE 488.2 commands (those beginning with *) to access the
higher- level summary registers (refer to the SCPI Reference). Access Lower- level registers by using
STATus commands.

Advertising
This manual is related to the following products: