Technical data, Power supply, Flow sensor power output – AW Gear Meters MX 9000 User Manual

Page 11: Frequency inputs, Analog output(s) 4-20 ma, Relay contact ratings, Mx 9000 process monitor

Advertising
background image

MX 9000 Process Monitor

Operation and Programming Manual

10

MX 9000 User Manual, Rev. 2.0 7/16/2013

Technical Data

Minimum Power Supply Requirements

16 VAC/250mA with supplied 110 VAC transformer, or

18-24 VDC/250mA. (customer supplied direct current)

120/240 VAC with option board 2

Flow Sensor Power Output

(2) @ 15 VDC/50 mA. each

Frequency Inputs

0-4.5 KHz, sine, square or saw-tooth; 5 volts minimum amplitude; 3.3K Ohm impedance

Analog Output(s) 4-20 mA

external-powered loop output into a maximum 500 Ohm load impedance with 24 volt supply

Relay Contact Ratings

Maximum

Switched

Power

Resistive Load

DC: 60W

AC: 125VA

Inductive Load

DC: 30W

AC: 60VA

Maximum Switched Voltage

100VDC, 250VAC

Maximum Switched Current

2A/DC, 1A/AC

Rated

Load

Resistive Load

DC: 30V, 2A

AC: 125V, 1A

Inductive Load

DC: 30V, 1A

AC: 125V, 0.3A

Figure 1: Relay Contact Ratings

NOTE: Maximum wire gauge 16 AWG

LOWER TERMINAL BLOCK CONNECTIONS:


Pin 1:

(+) 18-24 VDC Supply Voltage / 16 VAC Input

Pin 2:

(-) 18-24 VDC Supply Voltage Ground / 16 VAC Input

Pin 3:

(+) Sensor 1 Supply Voltage 15 VDC 25 mA MAX

Pin 4:

Sensor 1 Signal Input

Pin 5:

(-) Sensor 1 Supply / Signal Common

Pin 6:

(+) Sensor 2 Supply Voltage 15 VDC 25 mA MAX

Pin 7:

Sensor 2 Signal Input Housing Ground

Pin 8:

(-) Sensor 2 Supply / Signal Common

Pin 9:

(+) External Reset Input

Pin 10:

(-) External Reset Input

Pin 11:

(+) mA Loop 1 Output Limit 1

Pin 12:

(-) mA Loop 1 Output Limit 1

Advertising