Fixed output source, Rate a (or b) source, Mx 9000 process monitor – AW Gear Meters MX 9000 User Manual

Page 27

Advertising
background image

MX 9000 Process Monitor

Operation and Programming Manual

26

MX 9000 User Manual, Rev. 2.0 7/16/2013

Fixed output source


Limits Programming menu

Figure 13: Fixed Output Source

This option allows the user to select a constant mA value the MX 9000 will output regardless of any
changing values. A constant mA signal could be used as an external indicator showing if the MX 9000 is
on. Allowable values are from 2mA to 20mA.

RATE A (or B) source


Limits Programming menu

Figure 14: Rate A or B Source

RATE source allows the user to configure the mA output to represent the flow rate value. The analog
output span can be scaled for either zero to max flow or a non-zero flow to max flow. If the flow rate
goes above the programmed maximum flow rate, the analog output will continue to increase, up to a
maximum of 22mA. This is useful for system fault detection.

Min Flow Rate

Enter the minimum user flow rate. This can be a non-zero value, such as the lowest application flow
rate if the equipment monitoring the mA signal can be programmed as such. It can also be entered as
zero, but in this case it will affect the accuracy of the mA reading vs flow accuracy. If a non-zero value is
entered, the user will also be asked to enter a mA value to represent zero flow.

Min Flow mA

Enter the mA to represent the above entered minimum flow rate. Value must be equal to or greater
than 2mA.

Max Flow Rate

Enter the maximum flow rate to monitor.

Max Flow mA

Enter the mA value to represent the above entered maximum flow rate value. 20mA is the maximum
allowable value.

Zero Flow mA

This screen only shows if the Min Flow Rate was programmed as a non-zero value. Enter the mA value
to represent zero flow. Lowest value allowable is 2mA (cannot be greater than the Min Flow mA value).

Fi xed mA Output

04.00 mA

Mi n Flow Rate
0000000.00 GPM
Mi n Flow mA
04.00 mA

MAX Fl ow Rate
0000100.00 GPM
Ma x Fl ow mA
20.00 mA

Zero Flow mA

04.00
SEE NOTE BELOW