Total source, Grand total source, Limit / pulse output programming – AW Gear Meters MX 9000 User Manual

Page 28: Mx 9000 process monitor

Advertising
background image

MX 9000 Process Monitor

Operation and Programming Manual

27

MX 9000 User Manual, Rev. 2.0 7/16/2013

TOTAL source


Limits Programming menu


Figure 15: Total Source

TOTAL source allows the user to configure the mA output to represent the Totalizer value. If the
totalizer value goes above the programmed maximum total value, the analog output will continue to
increase, up to a maximum of 22mA. This is useful for system fault detection.

Zero Total mA

Enter the mA value to represent a zero totalizer value. Minimum allowable value is 2mA.

Max Total Value

Enter the maximum totalizer value to monitor.

Max Total mA

Enter the mA to represent the above entered maximum totalizer value. 20mA is the maximum
allowable value.

GRAND TOTAL source

Limits Programming menu

Figure 16: Grand Total Source

GRAND TOTAL source allows the user to configure the mA output to represent the Grand Total value. If
the Grand Total value goes above the programmed maximum Grand Total value, the analog output will
continue to increase, up to a maximum of 22mA. This is useful for system fault detection.

Zero Grand Total mA

Enter the mA value to represent a zero Grand Total value. Minimum allowable value is 2mA.

Max Grand Total Value

Enter the maximum Grand Total value to monitor.

Max Total mA

Enter the mA to represent the above entered maximum totalizer value. 20mA is the maximum
allowable value.

Zero Total mA

04.00 mA

MAX Tota l Value
0001000.00 GAL
Ma x Total mA
20.00 mA

Zero Grand Total mA

04.00 mA

MAX Gra nd Total Value
0001000.00 GAL
Ma x Gra nd Total mA
20.00 mA