I/o manual adjustment, Analog output adjustment, Mx 9000 process monitor – AW Gear Meters MX 9000 User Manual

Page 35

Advertising
background image

MX 9000 Process Monitor

Operation and Programming Manual

34

MX 9000 User Manual, Rev. 2.0 7/16/2013

At the second mA adjustment screen, the MX 9000 outputs the value that should equal 20mA output.
Change the mA value on the screen to match the value shown on the user’s readout equipment and
press

ENTER

when done.

At the next screen, the MX 9000 outputs the corrected 4mA value for loop 1. At the last screen the MX
9000 outputs the corrected 20mA value for loop 1. If either measured output is still not close enough to
the required value, enter the calibration routine again for loop 1. When done, press

EXIT

until back at

STATUS screen.

Loop 2 is calibrated in an identical manner – just select “Calibrate Output Loop 2” in the IO Function
screen. NOTE: Loop 2 is only available if option boards 1 or 2 are present.

I/O Manual Adjustment

Whether for troubleshooting purposes or to manually control external equipment, the MX 9000 allows
the user to enter an I/O routine in which the analog output, Limit outputs and Frequency outputs can be
controlled and the external Reset input can be monitored. A good use of this feature is to verify
communication between the MX 9000 outputs and the users’ readout equipment in a controlled fashion
before final system installation.









mA Menu Status Screen Limit Menu Status Screen Reset Monitor Status Screen

Figure 28: I/O Manual Adjustment


When entering the I/O programming mode from the STATUS and password screens, use the

UP

or

DOWN

button to change the I/O Function to ‘Test output’ as shown above and press

ENTER

. Next

choose which I/O to change and press

YES

.

Analog Output Adjustment

The user can manually control the mA output to any value between 2mA to 20mA in one of two ways.
Fine adjustment allows user to program a specific mA value to output. Coarse adjustment allows user to
increment or decrement the mA value in 1mA steps using the

UP

and

DOWN

buttons. Use

SELECT

to

choose which control is desired. HINT: Coarse allows a quick way to step from 2 to 20 mA.

STATUS L1 OFF L2 OFF
RTA 000.00 TOA 00000
RTB 000.00 TOB 00000
ANLG 04.00 mA

ENTER PASSWORD:

11111

IO Function

> Tes t Output

Adjust mA Output?

NO YES
EXIT

Adjust Limits Output?

NO YES
EXIT

Moni tor Reset Input?

NO YES
EXIT