Decimal Places

This sets the number of decimal places in the display for numerical values. The choices are 1 through 3.
Use the

UP

and

DOWN

buttons to adjust.

Screen Color Settings

Customization of the backlight for the LCD for the screen is available. Color coding of the limit alarms
can be useful for visual indication of totals reached or rates that are out of tolerance. Default settings
are green for normal operation, blue for Limit one exceeded and red for limit 2 exceeded. Use

ENTER

to

move from line to line and

SELECT

to change colors as desired.

Calibrating Analog Output

The analog output can be calibrated to correct for any variances caused by the users input equipment.
The calibration routine allows the user to adjust the 4mA and 20mA output values.
The calibration routine is entered from the STATUS screen. NOTE: When entering the calibration
routine, any incoming frequency to the MX 9000 is ignored.
Before starting the calibration routine,
make sure the analog output is connected to the intended readout equipment. To calibrate the MX
9000 it is necessary to enter the analog value read from the user’s readout equipment.













IO Function Test Output

Figure 27: Calibrating Analog Output

From the run mode STATUS screen, press and hold the

ENTER

button for 3 seconds to reach the

password screen. Enter “11111” using the

DOWN – UP – SELECT

buttons then push

ENTER

. The I/O

Function programming screen will appear. Press the

UP

or

DOWN

button to display the ‘Calibrate

Output Loop 1’ choice and then press

ENTER

.

At the first mA adjustment screen, the MX 9000 outputs the value that should equal 4mA output.
Change the mA value on the screen to match the value shown on the user’s readout equipment and
press

ENTER

when done.

STATUS L1 OFF L2 OFF
RTA 000.00 TOA 00000
RTB 000.00 TOB 00000
ANLG 04.00 mA

ENTER PASSWORD:

11111

IO Function

> Tes t Output

IO Function

> Ca l ibrate Output
Loop 1


Tri m Analog Out 4mA

Press Enter When Ready

Enter measured mA
Va l ue for Loop 1

04.000

Trim Analog Out 20mA

Press Enter When Ready

Enter measured mA
Va l ue for Loop 1

20.000

Mea sure 4mA value
for Loop 1 a nd Press
ENTER

Mea sure 20mA value
for Loop 1 a nd Press
ENTER