Frequency output programming, Gate time filter, Mx 9000 process monitor – AW Gear Meters MX 9000 User Manual

Page 31

Advertising
background image

MX 9000 Process Monitor

Operation and Programming Manual

30

MX 9000 User Manual, Rev. 2.0 7/16/2013

TOTAL & GRAND TOTAL Limits

Select Limit Screen

Select Limit Screen

Figure 21: Total and Grand Total Limits

TOTAL / GRAND TOTAL Value

Enter the Total or Grand Total value at which the respective Limit output should change state. When
the Total or Grand Total is reset to zero, the limit pin changes back to initial state.

WARNING / ALARM AB / BA Value

The Warning or Alarm AB / BA limit will activate the selected relay when the respective limit is reached
in the Ratio AB and BA menus. Select the Warning or Alarm trigger desired and set the values in the
Ratio menus starting on page 35.

Frequency output programming

Select Limit Screen

Figure 22: Frequency Output Programming

The third output can only be set to output the incoming frequency from one of the two inputs. From
the top Limit programming menu, choose the Frequency Output option, press

ENTER

and use the

UP

or

DOWN

button to select the input channel to route to the frequency output. There are no other

variables to program. The output frequency is not affected by the Gate Time filter and cannot be
linearized. It is always the raw incoming frequency from the selected sensor.

Gate Time Filter

Linearizer Menu

Figure 23: Gate Time Filter


Tota l Value

0001000.00 GAL

Gra nd Total Value

0010000.00 GAL

Sel ect Li mit
Frequency Out
Sel ect Li mit Type
> Si gnal A

Ga te Time Filter A

(i n seconds)

001.0

Ga te Time Filter B

(i n seconds)

001.0