Quadrature signal programming, System settings programming, Mx 9000 process monitor – AW Gear Meters MX 9000 User Manual

Page 33

Advertising
background image

MX 9000 Process Monitor

Operation and Programming Manual

32

MX 9000 User Manual, Rev. 2.0 7/16/2013

the Linearizer will be turned OFF. The user has the ability to press

NO

button to cancel this option and

return to Point 1 programming screen.

Changing the linearizer table

To change a table Point value, enter the programming screen and press the

ENTER

button to get to the

table value to change. After changing the relevant values, continue pressing the

ENTER

button through

the remaining table values until reaching the end of the programmed table (first table point whose Freq.
is zero) to exit the table.

Adding linearizer table point

To add more table points, it must be noted that data can only be added to the end of a table. Therefore,
if the additional point(s) to add do not have a frequency greater than the last entered point, it will
require the user to manually “shift” the table points by entering the new points after the next smallest
existing value and then re-entering the remaining points.

If an existing table is changed and has more points than required, once the required points have been
entered and the next table value has the Freq. changed to zero, all remaining points will automatically
be reset to zero when exiting the table.

Quadrature Signal Programming


Figure 25: Quadrature Signal Programming

When used with two inputs on the same meter, the MX 9000 can display the flow direction if the signals
are 90° out of phase, due to the quadrature nature of the signals available on gear meters.


Enabling the quadrature signal display will automatically disable all screens associated with channel B as
it is required that when using quadrature signals it can only be with one flow meter.

System Settings Programming

Figure 26: System Settings Programming

The system settings menu allows for the customization of the decimal places and background color of
the LCD display during limit operation.

Qua drature Signal
Progra mming?
NO YES

Acti va te Quadrature?

NO YES

Notice

ENTER NUMBER OF
DECIMAL PLACES:
0

SCREEN COLOR SETTINGS
SCREEN COLOR: > Green
LIMIT 1 COLOR: Blue

LIMIT 2 COLOR: Red

Advertising