MX 9000 Process Monitor

Operation and Programming Manual

14

MX 9000 User Manual, Rev. 2.0 7/16/2013

Relay Outputs

Two form C relay outputs are available on option boards 1 and 2. They are programmed by the limit
screens as to the function of each. See Relay Contact Ratings on page 10 for limits.
















Figure 6: Relay Outputs

Analog Input (option board 1)

The analog input is available on option board 1. It can be configured for either a 4-20 mA input or a 0-5
or 0-10 VDC input. The input is referenced to the system common. Programming of the input is done
using JP1. For 4-20 mA, use jumper pins 1&3 and 2&4. For 0-5 VDC, use jumper pins 3&5 and 4&6. For
0-10 VDC, use jumper pins 3&5 only. Pins are identified on the printed circuit board. Remove back
cover to access.

Figure 7: Analog Input