2.3.

Wire the Protocol Converter

If you plan to use the EIA-485 port for Modbus RTU communication, CPI recommends an 18 AWG shielded,
twisted-pair stranded copper wire for the connection. CPI recommends no more than 2,000 feet (609.6m) of
wire at this specification.

2.3.1

Power Supply & Ground Connections

To provide power and ground connections to the Protocol Converter:

1. Connect an 18 AWG ground wire from the ground terminal to a suitable earth ground.

2. Connect power to the Protocol Converter in one of two ways, as shown in Figure 2.2:

a. Plug the wall adapter (provided) into the power jack on the Protocol Converter and into a UPS outlet.

b. Connect a dedicated 24VDC power supply to the + and - terminals to the left of the power jack.

IMPORTANT: CPI recommends powering the Protocol Converter from a UPS (uninterruptible
power supply) so the Protocol Converter can send alarm notifications during a power outage.

Figure 2.2 24VDC Power Supply Connection