RIM-Protocol Converter User Guide - Version 1.0

Chatsworth Products, Inc. (CPI) • 800-834-4969

53

Table 4.2 Read Output Registers Packet Structure

Table 4.3 Output Registers

4.3

RTU Framing

The example below shows a typical Query/Response from an Protocol Converter.

Table 4.4 Response Sample

Slave address 2 responds to Function Code 4 with six bytes of hexadecimal data and ends with CRC16 checksum.

Register Values:

40001 = 0000 (hex)
40002 = 0000 (hex)
40003 = 0001 (hex)

Code

Name

Description

Units

Range

40001

Integer Output

Register for Integer data

16

0-65535

42001

Float Output
* two registers need

Register for Float data

32

0-65535

Read Registers Request Packet

Read Registers Response Packet

Slave Address (1 byte)

Slave Address (1 byte)

03 (Function code) (1 byte)

03 (Function code) (1 byte)

Start Register (2 bytes)

Byte count (1 byte)

# of registers to read (2 bytes)

First register (2 bytes)

CRC Checksum (2 bytes)

Second register (2 bytes)

CRC Checksum (2 bytes)

Slave
Address

Function
Code

Count Bytes
of Data

Register
Data
Msb Lsb

Register
Data
Msb Lsb

Register
Data
Msb Lsb

CRC 16
“Lsb”

CRC 16
“Msb”

02

04

06

00 00

00 00

00 01

B5

A3