Table 3.7 BACnet Register Configuration Options

2. Click Submit Changes located in the upper left hand corner of the web page.

Option

Description

HTML Display

This option allows you to choose how the value is displayed on the register page.
Choose from Integer (whole number) or Float (a number plus a decimal).

Threshold 1

Indicates the value that, when reached or exceeded, causes the Protocol
Converter to trigger an alarm.

Specify if the alarm should occur when the reading is less than (<), Equal to (=)
or greater than (>) the specified threshold value.

Threshold 2

Indicates the value that, when reached or exceeded, causes the Protocol
Converter to trigger an alarm.

Specify if the alarm should occur when the reading is less than (<), Equal to (=)
or greater than (>) the specified threshold value.

Alarm Delay

The amount of time, in seconds, that passes between the time an alarm
condition occurs and the time the Protocol Converter issues an alert. The
default value of 0 indicates no delay.

Offline Delay

The amount of time, in seconds, that elapses before the Protocol Converter
considers the register to be stalled or offline.

The default value of 0 indicates no delay.

Current Age

Indicates the amount of time, in seconds, since the Protocol Converter last
received an updated value.

Local Modbus Int Register

The Modbus Integer data (whole number) used by a master device polling
the Protocol Converter.

Local Modbus Float Register

The Modbus Float data (number with decimal) used by a master device polling
the Protocol Converter.

BACnet Instance

The number used by a BACnet master for polling data from the Protocol
Converter.

Possible values include Analog Instance (AI) or Binary Instance (BI).

SNMP Register/Table OID

The OID (Object Identifier) being polled from a SNMP software. The Protocol
Converter displays the OIDs used for Integer data, Float data and the Label as-
signed.

SNMP Modbus Device
Register/Table OID

Formatted to
BASE.DEVICENUMBER.REGISTERNUMBER where
BASE is the OID for this table, DEVICENUMBER is the
device’s number in the Protocol Converter (1-32) and the
REGISTERNUMBER reflects the appropriate device point address.