Chatsworth Products Remote Infrastructure Management System Protocol Converter User Manual

Page 67

Advertising
background image

RIM-Protocol Converter User Guide - Version 1.0

Chatsworth Products, Inc. (CPI) • 800-834-4969

67

APPENDIX

C

TECHNICAL SPECIFICATIONS

Table C.1 Technical Specifications

Power

24VAC @ 600mA max, 50/60Hz, 24VDC @ 600mA max.

Communications Ports

Ethernet

10/100 BASE-T, RJ45 connector; 500VAC RMS isolation

EIA-232

DB9 female connector; 9600 baud; No parity, 8 data bits,
1 stop bit

EIA-485 (Dual Port Protocol
Converter containas 3 EIA-485 ports)

1200, 2400, 9600 or 19200 baud (selectable); Parity: none,
even or odd, 8 data bits, 1 stop bit. Port 2 is configurable for
half-duplex (2-wire) or full-duplex (4-wire)

Protocols

TCP/IP, HTML, TFTP, SNMP

V1: V2C MIB-2 compliant; NMS Manageable with Get

Modbus (EIA-485)

Modbus Master/Slave; RTU mode; Supports Master codes
01, 02, 03, 04 and Slave code 03

Modus TCP/IP UDP/IP

Modbus Master/Slave; TCP/IP transmission protocol

BACnet/IP

ASHRAE STD 135-2004 Annex J; Port 3 of Dual Port
Protocol Converter is BACnet MS/TP capable (Slave only)

SMTP (email)

Supports Client Authentication (plain and login); compatible
with ESMTP servers

Terminal Emulation

VT100 compatible (for configuration and diagnostics only)

Protocols In

SNMP, Modbus TCP/IP & RTU, BACnet

Protocols Out

SNMP, Modbus TCP/IP & RTU, BACnet; BACnet MS/TP
(Port 3 of Dual Port Protocol Converter only)

Login Security

Web Browser Access (Ethernet)

1 Web password Read Only; 1 Web password Read/Write

Terminal Emulation Access

None

Maximum Number of Units/Modules/Nodes

32

Maximum Number of Registers/OIDs/
Instances

1,024