Chatsworth Products Remote Infrastructure Management System Protocol Converter User Manual

Page 66

Advertising
background image

RIM-Protocol Converter User Guide - Version 1.0

66

www.chatsworth.com

Table B.1 Troubleshooting the Protocol Converter (continued)

Problem

Action

Slave units are showing loss
of communication.

1) Check the Device Configuration in the Protocol

Converter and make sure the proper addressing is
assigned.

a) Modbus-RTU/485: The device address is set to

the proper RTU address and the 485 communica-
tions line is wired properly.

b) Modbus TCP/IP: The Proper device address and

IP address has been assigned. Modbus TCP/IP-
communications requires port 502 of that IP
address to be enabled/open. Check with IT to
make sure there is not a firewall or port blocking
on port 502.

c) SNMP: Check the IP address and community that

was configured on the Protocol Converter for
communication. Port 161 of the IP address is
used for SNMP get data. Check to make sure this
port is open.

d) BACnet: Check the IP address and device number

configured on the Protocol Converter. The default
port used for BACnet data is port 47808. Check
with IT to make sure this port is open for
communication on the network.