Baldor GLC GENERATOR GLC45 User Manual

Page 14

Advertising
background image

2-4 General Information

MN2408

Room Location Often a separate building located on the site away from the main building is the most simple and

cost effective. Major considerations when housing the genset in a separate building are:

S

Maintain the building at a satisfactory temperature year round (to meet applicable

codes).

S

Assure the genset is not located so far from the emergency loads that reliability is

compromised.

S

The floor’s load carrying capacity must be checked and must exceed the weight of the

genset and its associated equipment.

S

Engine Cooling System

A genset with an engine mounted radiator is the least costly to install; however, the

room must be located in a place where sufficient radiator cooling air can be brought

into and exhausted from the room.

S

Exhaust System

The exhaust system must minimize exhaust restriction. Exhaust restriction must be

limited to 3 in. Hg (76 mm Hg) maximum, to ensure proper engine operation. The

exhaust system should be as short and have as few bends as possible.

S

Room Air

If the genset is cooled with an engine mounted radiator, and sufficient air is brought into

and exhausted from the room to satisfy the radiator cooling requirements and the

combustion air requirements, the room will not overheat when the genset is running.

If a remote mounted radiator or a heat exchanger is used, and adequate air is

circulated through the room to keep it at a reasonable temperature, there will be

adequate air for combustion.

S

Fuel Tanks (Diesel Only)

Locate the fuel storage tank as near the genset as possible. This will minimize the cost

of fuel system installation and will maximize fuel system reliability.

S

Controls and Transfer Switch

Locate the control switch gear as close to the emergency loads and the genset as

practical. This will minimize the chances that a failure of the power line to the

emergency load will go undetected. In locating the switchgear, accessibility for service

and maintenance must be considered.

S

Genset Noise

Internal combustion engines produce noise, so the room should be located away from

occupied buildings. In addition the genset room can be treated to reduce noise

transmission. In locating the genset room, both engine, fan and exhaust noise must be

considered.
If noise within the genset room, or noise transmitted to the surrounding parts of the

building are a concern, then the room must be made large enough to allow for

installation of noise attenuating walls and noise absorbing walls.

Light weight concrete blocks filled with sand or special “sound block” concrete blocks

are commonly used. Noise attenuating, tight fitting windows and doors also help reduce

noise transmission to the rest of the building.

A double–walled room should be considered. Vibration isolators under the genset rails

will also reduce the transmission of noise through the floor.

S

Code Requirements

Building and safety codes deal with engine location. These requirements are

concerned with fire rated walls, a location that minimizes the possibility of damage to

the genset and interruption of the emergency system due to storms, foods, fire,

vandalism, etc.
Codes often deal with the need to maintain certain temperatures in the genset room

and with fuel system location. The most important codes in the USA are the National

Fire Protection Association Code Numbers 99 and 110, but local codes must also be

observed.

Advertising