Baldor GLC GENERATOR GLC45 User Manual

Page 68

Advertising
background image

4-22 Operation

MN2408

Operator Control Panel (Analog Engine Controller Only)

Figure 4-10 Analog Operator Control Panel

+

OFF

1

2

3

Panel Lights switch (On-Off )

Turns on two lamps to illuminate the operator panel.
Panel Light Fuse

Fuse for panel lights.
Master Control switch (Manual Run-Stop - Auto Start)

Manual Run - Starts the engine manually.

Stop - Stops the engine and generator.

Auto Start - Starts the engine when the Remote start" terminals are

closed.

Display Lamps

High Temperature - Indicates excessive engine coolant temperature.

Low Oil Pressure - Indicates low engine oil pressure.

Overspeed - Indicates engine speed is greater than preset limit.

Overcrank - Failure of the engine to start by the end of the crank period

results in an overcrank" shutdown and alarm indication.

Voltage Adjust

Increase or Decrease the Generator output voltage (displayed on

VOLTAGE meter)

AC Voltage meter

Analog display of generator output voltage in RMS volts.
AMMETER switch (3 position)

Off - No current is measured by the Amperage meter.

1 - Phase 1 current is measured by the Amperage meter.

2 - Phase 2 current is measured by the Amperage meter.

3 - Phase 3 current is measured by the Amperage meter.
Amperage meter

Analog display of generator output current in RMS amps.
Hertz meter

Analog display of generator output frequency in Hertz.
Battery Voltage meter

Displays the voltage of the engine starting battery.
Engine Temperature meter

Displays the temperature of the engine coolant.
Oil Pressure meter

Displays engine oil pressure.
Run Time (Hours) meter

Total elapsed time indicator of generator set operation.

PANEL LIGHTS

ON

OFF

MASTER

CONTROL

MANUAL

RUN

AUTO

START

STOP

OVERSPEED

OVERCRANK

HIGH TEMPERATURE
LOW OIL PRESSURE

VOLTAGE

AMPERAGE

AMMETER

HERTZ

PANEL LIGHT

FUSE

VOLTAGE

ADJUST

Oil Pressure

Battery

Volts

Engine

Temp

RUN TIME (HOURS)

Panel Light

Panel Light

Operating Procedures The engine–generator controller is designed to start and stop an engine from either a local

(“Manual”) or remote (“Automatic”) mode. When a start command is issued, the controller issues

a run and crank output signal. The controller then monitors engine speed and when crank

disconnect speed is reached, the crank signal is terminated. While the engine accelerates to

normal speed, the controller continuously monitors the engines speed signal. Should the engine

speed exceed the maximum predetermined setpoint, the overspeed shutdown fault circuit will

activate, terminating the run signal.
In addition to overspeed shutdown, the engine controller also monitors many other engine

protection circuits and should they be activated, the engine will be stopped and/or alarm initiated.

The engine will automatically stop for any shutdown condition, or when the remote and/or local

start signal is removed. The engine controller operation includes time delay circuits for normal

operating conditions such as start delays, cool down and cranking periods.