Operation 4-23

MN2408

Manual Start/Stop

To manually Start the Gen–Set, set the Master Control switch to the “Manual Run” position. The

following happens:

1.

When the “Manual Run” push–button is pressed, an Engine Start Delay timer is

initiated. (The start sequence will not be initiated if any shutdown fault condition is

present.)

2.

When the engine start delay time expires, an engine RUN and CRANK output signal

will be initiated. (The RUN output may be programmed to only energize when a start

signal is initiated and an engine speed signal is detected.)

3.

When the engine starts and begins to accelerate to nominal speed, the controllers

speed sensor will terminate the CRANK output when engine speed reaches

approximately 20% speed (i.e. CRANK DISCONNECT speed setpoint).

To manually Stop the Gen–Set, set the Master Control switch to the “Stop” position. The

controllers RUN output will be immediately terminated which will initiate the engine stop

sequence. The engine is locked out and will not run with the Master Control switch in “Stop”.

Automatic Start/Stop

To setup the generator for automatic operation, set the Master Control switch to the “Auto Start”

position. The following happens:

1.

The engine will automatically start upon activation of the remote start contact input. The

remote device initiates a start sequence upon contact closure.

2.

When the remote start signal is activated, the engine will start as per the sequence of

operation described for the manual start sequence.

3.

The automatic stop sequence will be initiated by removal of the remote start signal.

4.

When the start signal is removed, a cool down delay function will be initiated.

5.

When the cool down time delay period expires (typically 5 minutes), the controllers

RUN output will be immediately terminated which will initiate the engine to stop.

Automatic Fault Shutdown

When a fault circuit is programmed as a SHUTDOWN, the engine will immediately stop when the

fault is activated. A specific shutdown fault can be programmed with a definite time transient

delay period that must expire before the shutdown is activated. The stop sequence will cause the

controllers RUN output to be immediately terminated which will cause the engine to stop.

Figure 4-11 9957N Analog Engine Controller Connections

5

4

3

2

1

12

11

10

9

8

7

15 14 13 X1

Fuel Relay

Remote Start

Contact

10A

Start Relay

Display

LED’s

Low Oil Pressure

High Water Temperature

Overcrank

Overspeed

RUN (Engine Started – Not Used)

Common Alarm (Not Used)

Starting Battery

Magnetic

Pickup

External Components

Auto

Off

Manual

High Water

Temperature

Low Oil

Pressure

6

Oil Pressure Water Temperature Delay

Overspeed

Crank Disconnect

Single (On) or Cycle Crank (Off)

Overspeed Verify (Off = True Speed,

On = 13% increase)

Crank Cycle

Crank Attempts

3

1

Off

2

Off

Switches shown in

OFF position

Crank Attempts

2

Off

On

3

Off

Off

4

Off

On

1

Off

Off

On

On

5

On

Off

6

On

On

7

On

Off

8

On

On

Off

Off

On

On