5-4 Troubleshooting and Maintenance

MN2408

Note: See Engine Controller manual for additional information.

Table 5-3 Troubleshooting Guide (Analog Controller Only)

Problem

Possible Cause

Remedy

Controller cannot be Reset"

Engine not stopped

Controller not in OFF mode

Verify the engine is at a complete stop before trying to reset.

Set the controller to the OFF mode before trying to reset.

Engine alarms are ON for high engine

temperature or low oil pressure when

engine is operating properly

Sending unit is disconnected (open

circuit)

Defective sending unit

Verify the sending units wiring to controller terminals is not open or

shorted.

Verify the engine mounted senders have correct resistance values

for corresponding input temperature or pressure.

Overspeed shutdown occurs at normal

speed

Controller has failed or input from

Magnetic pickup is incorrect.

Verify the adjustments. Replace controller if failed.

Service

Service for your generator can be obtained from the service department at Baldor Generators by

calling (920) 236–4200. Please have the following information available prior to contacting the

factory:

The model number and serial number of the generator set.
A complete and accurate description of the problem.

Parts

Parts for your generator can be obtained from the service department at Baldor Generators by

calling (920) 236–4200. Please have the following information available prior to contacting the

factory:

The model number and serial number of the generator set.
A complete and accurate description of the part (part number if known).

Note: Engine parts can usually be obtained from a local distributor by using the information in

the engine manufacturer’s owner’s manual.

Advertising