Operation 4-11

MN2408

Generator AC Metering The controller is in the display mode at all times except when in the programming

mode. The display screens and menus may be selected by pressing the Enter or Exit keys to

access Operating Status Display, Fault Display, Timer Countdown, Generator AC Metering or

Programming Menus. The LCD display shows the status of the generator output:

Vavg

000

Aavg

000

Freq

000

Generator Average Output Display

Average Voltage

Displays the average generator voltage as follows:

3-phase system: AVERAGE LINE TO LINE VOLTAGE--Phases

1-phase system: LINE TO LINE VOLTAGE--Phases A to B

Average Current

Displays the average generator current as follows:

3-phase system: AVERAGE LINE CURRENT--Phases A,B,C

1-phase system: AVERAGE LINE CURRENT--Phases A,B

Frequency

Displays generator frequency in hertz (HZ). The frequency is displayed with a resolution of 1/10 of a hertz.

KVA

632.23

Generator KVA Display

KVA

Displays the generator's total power output in kilo-voltamperes (KVA).

Generator Phase Voltage Display

(Line to Line)

Vab

600

Vbc

600

Vca

600

Vab

Displays the generator's output voltage:

3-phase system: LINE TO LINE VOLTAGE--Phases A to B

1-phase system: LINE TO LINE VOLTAGE--Phases A to B

Vbc

Displays the generator's output voltage:

3-phase system: LINE TO LINE VOLTAGE--Phases B to C

1-phase system: LINE TO NEUTRAL VOLTAGE--Phases A-N

Vca

Displays the generator's output voltage:

3-phase system: LINE TO LINE VOLTAGE--Phases C to A

1-phase system: LINE TO NEUTRAL VOLTAGE--Phases B-N

Generator Phase/Neutral Voltage Display

(Line to Neutral)

Van

347

Vbn

347

Vcn

347

Note: The generator's neutral must be connected to controller terminal TB1-VN and the neutral connected" prompt in the main

program menu must be selected as Yes".

Van

Displays generator voltage Phase A to Neutral.

Vbn

Displays generator voltage Phase B to Neutral.

Vcn

Displays generator voltage Phase C to Neutral.

Generator Phase Current Display

a

408

b

451

c

415

Amps

Amps a

Displays generator load current as follows:

3-phase system: PHASE A CURRENT

1-phase system: PHASE A CURRENT

Amps b

Displays generator load current as follows:

3-phase system: PHASE B CURRENT

1-phase system: PHASE B CURRENT

Amps c

Displays generator load current as follows:

3-phase system: PHASE C CURRENT

1-phase system: not applicable

Generator Frequency/Hourmeter Display

FREQ

HOURS

60.1 Hz

56788 Hrs

FREQ

Displays generator frequency in hertz (HZ). The frequency is displayed with a resolution of 1/10 of a hertz.

HOURS

Displays unit operating hours.