Baldor GLC GENERATOR GLC45 User Manual

Page 66

Advertising
background image

4-20 Operation

MN2408

Figure 4-6 Analog Fault Menu Loop Parameters

Fault Name

Input Analog

Type

Fault

E Enable

Setpoint Level

(Pick up)

Setpoint Level Action

S Shutdown

Alarm Latch

Y Yes

Bypass On

Start

Transient

Delay (Sec)

Type

E=Enable

D=Disable

(Pick-up)

(Drop-out)

S=Shutdown

A=Alarm

Y=Yes

N=No

Start

Y=Yes

Delay (Sec)

D=Disable

A=Alarm

N=No

Y=Yes

N=No

Under Voltage

AC Voltage

E*

S

Y

Y*

5.0

Under Frequency

AC Frequency E*

S

Y

Y*

5.0

Weak Battery

DC Voltage

E*

18.0

N/A

A*

Y

N*

3.0

Low Battery

Voltage

DC Voltage

E*

25.6

N/A

A*

N

N*

120.0

High Battery

Voltage

DC Voltage

E*

30.4

N/A

A*

N

N*

10.0

Low Engine Temp

Temp Sender

E*

95 °F

N/A

A*

Y

N*

5.0

High ENG Temp #1

Alarm

Temp Sender

E*

198 °F

N/A

A

Y

Y

2.0

High ENG Temp #2

Shutdown

Temp Sender

E*

206 °F

N/A

S

Y

Y

2.0

Low Oil Press #1

Alarm

Press Sender E*

30PSI

N/A

A

Y

Y*

2.0

Low Oil Press #2

Shutdown

Press Sender E*

20PSI

N/A

S

Y

Y*

2.0

* Indicates parameter is non-programmable.

Figure 4-7 Digital Fault Menu Loop Parameters

Fault Name

Input #

Action

S Shutdown

Alarm Latch

Y Yes

Polarity

O Open

Bypass On

Start

Transient

Delay (Sec)

S=Shutdown

A=Alarm

Y=Yes

N=No

O=Open

C=Close

Start

Y=Yes

Delay (Sec)

A=Alarm

N=No

C=Close

Y=Yes

N=No

Low Oil Pressure

1

S

-

O

Y

0.5

High ENG TEMP

2

S

-

O

Y

1.0

Batt Chgr Input Fail 3

A

Y

C

N

30.0

Low Fuel Level

4

A

N

C

N

0.1

Figure 4-8 Calibration Menu Loop Parameters

Parameter

Setting

Volts A-B

Zero XXX

XXXVAC

Volts A-B

Span XXX

XXXVAC

Volts B-C

Zero XXX

XXXVAC

Volts B-C

Span XXX

XXXVAC

Volts C-A

Zero XXX

XXXVAC

Volts C-A

Span XXX

XXXVAC

Volts A-N

Zero XXX

XXXVAC

Volts A-N

Zero XXX

XXXVAC

Volts B-N

Zero XXX

XXXVAC

Volts B-N

Zero XXX

XXXVAC

Volts C-N

Zero XXX

XXXVAC

Volts C-N

Zero XXX

XXXVAC

Current A

Zero XXX

XXXAAC

Current A

Span XXX

XXXAAC

Current B

Zero XXX

XXXAAC

Current B

Span XXX

XXXAAC

Current C

Zero XXX

XXXAAC

Current C

Span XXX

XXXAAC

Battery Voltage

Span XXX

XX.X VDC

Engine Temperature

XXX

XXX C/F

Oil Pressure

XXX

XXXX PSI/KPA

Advertising