General Information 2-7

MN2408

Designing An Isolated Foundation
If the genset cannot be mounted directly on a floor slab, or if it is desirable to isolate it from the

floor slab, then a separate foundation slab must be designed.
A massive concrete foundation is not required. Outside dimensions of the foundation should

exceed the outside genset dimensions by 12in (300mm).

For single genset installation, the foundation weight should be a minimum of 1.50 times the

genset wet weight.

For multiple genset installation, the foundation weight should be a minimum of 2.0 times the

genset wet weight.

Figure 2-3 shows a method to calculate foundation thickness and the soil bearing load of the

foundation and generator set. The soil load bearing capacity under the foundation must equal or

exceed the load from the foundation and genset. If it does not, then a footing, as shown in Figure

2-4 must be added to spread the load over a larger area.

Figure 2-3 Calculate Soil Bearing Load (SBL) Capacity

Figure 2-4 Typical Footing on Foundation in Soil With Low Soil Load Bearing Capacity