Receiving & Installation 3-7

MN2408

Example: Determining Pipe Size for Natural Gas

A generator has a 16Hp engine 60 feet from the supply.

Determine the supply pipe size for Natural Gas fuel.

16 x 10,000 = 160,000 BTU’s / per hour for proper operation.

160, 000

1, 096 +

146 cubic feet per hour.

From Table 3-6, a 60 foot run requires a minimum 1” pipe at full engine load.

Natural Gas Connections

The incoming pressure must be 11 inches water column (6 oz. pressure).

Table 3-5 Natural Gas Flow Rate (Cubic Feet per Hour) per Pipe Length

Pipe

Length

Iron Pipe Size

Length

(Feet)

1

/

2

3

/

4

1

1–

1

/

4

1–

1

/

2

2

2–

1

/

2

3

4

6

8

15

73

165

332

722

1174

2386

3704

6253

13352

37229

30

50

115

232

515

818

1712

2646

4521

9331

26330

53728

45

41

95

191

418

673

1419

2213

3752

7600

22462

43867

60

37

83

166

366

587

1241

1924

3319

6542

18595

37999

75

74

149

332

524

1077

1684

2886

5772

16652

33959

90

67

137

298

433

962

1501

2597

5291

15200

31025

105

63

126

274

885

1376

2357

4906

14064

28715

120

115

260

404

827

1289

2213

4618

13160

26859

150

105

233

366

750

1174

2011

4185

11775

24050

180

96

216

337

693

1077

1876

3848

10736

21934

210

89

197

308

635

991

1712

3559

9937

20298

240

183

289

596

933

1616

3357

9235

18990

270

171

274

558

875

1520

3127

8658

17903

300

164

260

524

827

1433

2886

8177

16998

Note: Almost all operation problems are related to the installation techniques used. Do Not

guess, be sure pipe size is adequate for required flow rate.

1.

Connect the proper size gas pipe at the Inlet Connection to the Fuel Lock Solenoid.

Connect the Natural Gas pipe line shown in Figure 3-3 using the correct size pipe for

the required flow rate and length of pipe. Refer to Table 3-5 for pipe size. Be certain

that all connections are sealed and no leaks are present. The installer must ensure

that all gas connections comply with all building codes.

2.

Verify Fuel Supply Pressure

Prior to initial operation of generator, verify that fuel system pressure is 11

″ Water

Column (6 oz. pressure) and fuel pipe sizes comply with Table 3-5.

3.

Proceed to Electrical Connections.

Figure 3-3 Gas Line Connections

Solenoid, Fuel Lock

Inlet Connection

Air Cleaner

Carburetor

Mounting Bracket

Additional Valve

(Safety Shutoff Valve)

Supply Piping

U.L. requires a second shutoff valve and regulator to be installed in the supply piping to

control the gas supply to the generator.

Additional Regulator

(11 - 14" water column pressure)

External Supply Piping (by installer)