Baldor GLC GENERATOR GLC45 User Manual

Page 43

Advertising
background image

Receiving & Installation 3-11

MN2408

Battery Charger Considerations

1.

Mount the battery charger on the generator or as close to the generator as possible.

2.

If you mount the battery charger inside the building, mount it near the main breaker box

or disconnect box.

3.

If you mount the battery charger outside, you must protect it from the environment and

the elements.

4.

Do not mount the battery charger where flammable liquids or vapors are present.

General Wiring Considerations

1.

When routing the interface wiring, do not route it up against anything that could cut or

chafe the wiring. do not route the wire up against any hot or potentially hot object.

2.

Make sure that all the electrical components (generator set, transfer switch, battery

charger, etc.) share a common hard wired ground.

3.

Check with your local building inspector to determine what you must do to comply with

the local regulations for grounding of this type of permanent installation.

Frame Ground Connection
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power

before you ensure that grounds are connected. Electrical shock can cause serious or fatal

injury. NEC requires that the frame and exposed conductive surfaces (metal parts) be

connected to an approved earth ground. Local codes may also require proper grounding of

generator systems.

It is important for safety reasons that the Generator set, transfer switch and battery charger share

a common Ground and neutral.

The NEC requires that the frame and exposed metal surfaces be at local ground reference

potential to avoid electrical shock hazard. A local ground reference may require a driven earth

ground conductor at the generator installation site. Make the ground connection as shown in

Figure 3-5. Use the appropriate size wire as required by NEC and local codes.

Warning: Do not connect the generator output neutral to the frame or local ground. The generator

output is isolated from ground. NEC and local codes require that the generator output remain

isolated from local ground reference.

Figure 3-5 Frame Ground Connection

Earth Ground

Frame

Stud

Washer

Ground Wire Lug

Nut

Washer

1.

Open the enclosure access panel door 2 ( Figure 3-2).

2.

Connect the ground wire to the “earth ground” terminal shown in Figure 3-5.

This ground is the local reference ground to ground the generator frame only.