Operation 4-9

MN2408

Display Modes

The controller is in the display mode at all times except when in the programming mode. The

display screens and menus may be selected by pressing the Enter or Exit keys to access

Operating Status Display, Fault Display, Timer Countdown, Generator AC Metering or

Programming Menus. The LCD display shows the status of the generator output:

Operating Status The controller will power–up into an Emergency Stop failure mode, preventing possible engine

operation. The controller must be manually reset before normal operation can be established. To

reset the Emergency Stop condition, press the “OFF” push–button first, then press both

“INCREMENT” and “ENTER” push–buttons simultaneously. The controller will then reset, if a

remote emergency stop condition is not activated. The Utility Ready to Load programmable

output will energize if the remote start contact is open. The Main LCD Display will be shown.

Action

Description

Display

Comments

Apply Power and

Reset faults.

Main LCD Display.

Vavg

000

Aavg

000

Freq

000

Press Enter key

Show Operating Status screens

UNIT READY

Controller is in Auto" position and there

are no active faults.

Press

↑ or ↓ key

Scroll to next.

SWITCH IN OFF

Controller is in OFF" position from the

front panel keypad push-button.

Press

↑ or ↓ key

Scroll to next.

UNIT RUNNING

Engine is running and all conditions are

normal.

Press

↑ or ↓ key

Scroll to next.

UNIT SHUTDOWN

A shutdown fault is active. The specific

fault will be automatically displayed.

Press

↑ or ↓ key

Scroll to next.

UNIT ALARM

One or more faults are active. The

display will automatically scroll through

all active faults at a two second rate.

Fault Display The fault display menu is automatically displayed when an alarm or shutdown fault is activated.

The specific alarm or shutdown fault label will be displayed and if multiple alarm conditions are

present, the display will automatically scroll through all active faults.