Baldor GLC GENERATOR GLC45 User Manual

Page 23

Advertising
background image

General Information 2-13

MN2408

Remote Radiator Cooling
Remote Radiator Airflow generally assumed there will be no external restrictions to airflow. If this

is not true, restriction must be considered in sizing and selection of a cooling fan and drive motor.

Typical examples of restrictions include landscaping, nearby buildings, air turbulence created by

buildings or other structures, and sight or noise “screens”. See Figure 2-9.
Remote Radiator Fan Motor. Remote radiator cooling systems require the use of an electrically

driven fan. This fan must be connected to the emergency power source. Size of the motor is

determined by the fan size and fan speed.

1.

To specify a radiator to cool the coolant you will need to determine the amount of heat

rejected to the coolant. This is listed on the Engine Data Sheet as Heat Rejected to

Coolant in BTU/min. for engines using dry or water cooled type exhaust manifolds, as

applicable.

2.

Determine the minimum water flow required at the engine, and the maximum top tank

temperature. Using this information, determine the heat rejection capacity required of

the radiator. Radiator systems should be sized with approximately 15% greater

capacity than the engine’s maximum full load heat rejection to allow for overload and

cooling system deterioration. Whether water flow is produced by an engine mounted or

auxiliary pump, total piping system friction loss must be calculated. To do this, genset

location, remote radiator location and friction loss within the radiator, and piping system

must be estimated.

3.

Pressure drop through the radiator must be obtained from radiator manufacturer.

4.

If total piping system pressure exceeds the allowable Maximum Coolant Friction Head

External to the engine as listed on the Engine Data Sheet, the coolant piping size

should be increased and/or a radiator with less restriction must be used.

5.

Pressure drop in pipelines may be determined by the use of information in Table 2-2

Figure 2-11, and friction of water tables which may be found in most mechanical

handbooks such as “Cameron Hydraulic Data” handbook.

Table 2-2

Fitting Size

Flow Restriction of Fittings Expressed as Equivalent of Straight Pipe (in inches)

g

1.5

2

2.5

3

4

5

6

8

10

12

14

16

90 Elbow

4.4

5.5

6.5

8

11

14

16

21

26

32

37

42

45 Elbow

2.5

3

3.8

5

6.3

7.5

10

13

15

17

19

Long Sweep Elbow

2.8

3.5

4.2

5.2

7

9

11

14

17

20

24

27

Close Return Bend

13

15

18

24

31

37

51

61

74

85

100

Tee–Straight Run

3.5

4.2

5.2

7

9

11

14

17

20

24

27

Tee–Side Inlet or Outlet

9.3

12

14

17

22

27

33

43

53

68

78

88

Globe Valve Open

55

67

82

110

140

Angle Valve Open

27

33

41

53

70

Gate Valve Fully Open

1.2

1.4

1.7

2.3

2.9

3.5

4.5

5.8

6.8

8

9

Gate Valve Half Open

27

33

41

53

70

100

130

160

200

230

260

Check Valve

19

23

32

43

53

Hot Well Installations

One final consideration on the water side is the Maximum Static Head. This is the maximum

height allowable from the engine crank center line to the highest point in the coolant system. The

maximum static head is specified on generator specification sheets. If this number must be

exceeded, a hot well tank system must be used. A typical example is shown in Figure 2-12.
The design of hot well tanks and piping systems is somewhat complex. Your authorized Baldor

Distributor has experience in the design and installation of hot well systems. Consult your Baldor

Distributor if the static head of the coolant system in your genset application exceeds this criteria

and requires a hot well system.

Advertising