Baldor GLC GENERATOR GLC45 User Manual

Page 65

Advertising
background image

Operation 4-19

MN2408

Figure 4-5 Main Menu Loop Parameters

Parameter

Setting

Range

System Voltage (Line To Line)

XXXXX VAC

120–15000VAC

System Frequency

50Hz/60Hz

Toggle Between 50/60 Hz

System Phases

1 Phase/3 Phase

Toggle Between 1 & 3 Phase

y

Neutral Connected

Toggle Between Yes/No

Voltage Sensing

Voltage Sensing Pt Ratio

Ratio XXX

Enter Number 1–208 (1=Direct)

Current Sensing

Current Sensing Ct Ratio

Ratio XXX

Enter Number 1–999 (1=Direct)

Temperature Scale

Deg C/Deg F

Toggle Between Deg C/Deg F

Pressure Scale

PSI/KPA

Toggle Between Psi/Kpa

Start Delay

XXX Seconds

0–999 Seconds

Crank Time

XX Seconds

0–99 Seconds

Rest Time

XX Seconds

0–99 Seconds

Starter Re–engage Delay

XX Seconds

0–99 Seconds 0=Disabled

Number Of Cranks

XX Cranks

0–99 Times 0=Continuous

Bypass Delay

XX Seconds

0–99 Seconds

Cool down Delay

XX Seconds

0–9999 Seconds

Nominal RPM

XXXX RPM

0–4000RPM

Flywheel Teeth (Engine Speed

Sensing, Magnetic Pick Up

XXX Teeth

0–999 Teeth

Crank Disconnect

XX %

0–100%

Overspeed

XX %

100–150%

Overspeed Transient

X.X Seconds

0.0–9.9 Seconds

Run Output

Fail Safe Yes/No

Toggle Between Yes/No

Loss Of Speed Signal

Shutdown Alarm/Shutdown

Toggle Between Alarm/Shutdown

Common Fail For

Not In Auto Yes/No

Toggle Between Yes/No

Horn For Not In Auto

Toggle Between Yes/No

Prog Output #1

Common Fail (Factory setting)

Prog Output #2

Common Fail (Factory setting)

Prog Output #3

Common Fail (Factory setting)

Prog Output #4

Common Fail (Factory setting)

Prog Output #5

Common Fail (Factory setting)

Prog Output #6

Common Fail (Factory setting)

Warm–up Delay

0–99 Seconds

Neutral Delay

0–99 Seconds

Return Delay

0–999 Seconds

Reset Run Hours

Access by Master Password Only

Yes/No

Toggle Between Yes/No