Baldor GLC GENERATOR GLC45 User Manual

Page 51

Advertising
background image

Operation 4-5

MN2408

No Load Test

To allow a timed No Load Test of the engine/generator set while using the AMF control

application, a digital input contact from an external timer must be programmed for NO LOAD Test

The sequence of operation for a No Load Test condition is as follows:

1.

With the utility supply normal and the generator stopped, a no load test sequence may

be initiated by closing an external exercise timer contact to the programmed digital

input for No Load Test.

2.

After the external exercise timer contact closes, the engine will start and come–up to

normal operating speed and voltage. The controller will issue an alarm of a No Load

Test condition. The connected transfer switch will remain on the utility and the

generator will not transfer on load. Note: should the utility supply fail, the generator will

automatically transfer on load.

3.

The engine will continue to run as long as the external exercise timer contact remains

closed.

4.

After the external exercise timer contact opens, the engine will continue to run for its

cool down time as programmed, then it will automatically stop.

Standard Faults

When a fault occurs, information about the fault is displayed. The engine controller has many

analog and digital inputs for monitoring and control operations. Three types of faults are used:

1.

Internal Faults are derived from a combination of digital and analog inputs.

2.

Digital Input Faults are initiated from external contact inputs.

3.

Analog Input Faults are initiated from external analog signal inputs.

Figure 4-3 shows how the controller inputs and outputs are organized.

A description of each is provided.

Internal Faults

Overspeed Shutdown

Overspeed Shutdown is initiated when the engine's speed has increased above the overspeed setpoint. The overspeed fault

circuit is internally programmed as a latching shutdown fault. The overspeed shutdown fault circuit is programmable for the

percentage of nominal engine speed (i.e. overspeed setpoint) and for the transient time delay period. The programming

prompts for overspeed are located in the main menu programming loop.

Loss of Speed

Loss Of Speed is initiated when the engine's speed sensing circuit does not detect a speed signal for a period more than 2

Alarm/Shutdown

seconds following a run signal. The loss of speed fault may be user programmed as a latching shutdown fault or alarm only.

The programming prompts for loss of speed are located in the main menu programming loop.

Overcrank Shutdown

Overcrank Shutdown is initiated when the engine fails to start after the selected crank time or number of crank cycles. The

overcrank fault circuit is internally programmed as a latching shutdown fault and is not user programmable.

Switch not in AUTO

Switch not in AUTO is initiated when the controller's operating mode switch is changed from the auto position to any other

position (ON the keypad). This fault is internally programmed as a non latching alarm. In the main programming loop, this

alarm may be user programmed to initiate the common fail output relay.

Digital Input Faults

Four digital faults are provided and these are user programmable. Each digital fault input circuit is activated by a remote

Digital Inputs (N/O or N/C)

sensing contact that is external to the controller. Each digital fault input circuit may be programmed with a unique fault label

description as stored in the controller's non-volatile memory.

Factory settings have four standard digital faults as follows:

Fault

Name

Fault

Action

Digital Inputs

Terminal #

Low Oil Pressure

Shutdown

1

High Engine Temperature

Shutdown

2

Battery Charger Input Fail

Alarm

3

Low Fuel Level

Alarm

4

The following is a list of all digital faults:

High Bearing Temp

Failed To Sync

Reverse Power

Bat Charger Input Fail

High Cooler Vibration

Low Fuel Press

Fail To Sync

Bat Chrg Trouble

High Engine Temp

Low Engine Temp

Vent Damper Fail

Bat Charger Fail

High Engine Vibration

Low Oil Pressure

Gen Breaker Open

DC Fail

High Fuel Level

Low Fuel Level

Ground Fault

Breaker Tripped

High Oil Level

Low Oil Level

No Load Test

Basin Rupture

High Oil Temp

Fuel Leak

ATS In Bypass

High Winding Temp

Low Fuel Press

Remote Emerg. Stop

*Highintkmanftemp

Low Coolant Level

Air Damper Tripped

Blank" (i.e. no text for unused inputs)

Advertising