Baldor GLC GENERATOR GLC45 User Manual

Page 63

Advertising
background image

Operation 4-17

MN2408

Engine Temperature & Oil Pressure Calibration

To accurately calibrate the controller’s temperature sensor, an external temporary engine mounted
temperature gauge is required. The external temperature gauge should be connected as close as possible
to the temperature sender.
To accurately calibrate the controller’s pressure sensor, an external temporary engine mounted pressure
gauge is required. The external pressure gauge should be connected as close as possible to the pressure
sender.

ENGINE TEMP

127 95

5C

Displays the type of calibration function.

Displays the calibration correction factor number (0-255) used to obtain the correct Temperature or Pressure reading.

Displays the actual temperature or pressure measurement shown on the display menus.

This reading may be calibrated higher or lower by changing the correction factor number.

Engine Temperature

The engine temperature analog circuit must be calibrated with the engine temperature sender mounted on the engine.

Connect a temporary engine mounted temperature gauge of suitable accuracy and start the engine. After the engine

reaches normal operating temperature, enter the programming mode and scroll to the Engine Temperature Offset"

calibration point. Use the INCREMENT or DECREMENT push-buttons to adjust the correction factor number while

observing the displayed temperature. Adjust the correction factor number to obtain the identical temperature reading as

measured with the external temperature gauge. With the correct temperature displayed, press the Enter" push-button to

accept the correction factor number. Record the correction factor on the programming sheet for future reference.

Oil Pressure

Connect a temporary engine mounted pressure gauge of suitable accuracy and start the engine. After the engine

reaches normal operating pressure and temperature, enter the programming mode and scroll to the Engine Pressure

Offset" calibration point. Use the INCREMENT or DECREMENT push-buttons to adjust the correction factor number

while observing the displayed pressure. Adjust the correction factor number to obtain the identical pressure reading as

measured with the external pressure gauge. With the correct pressure displayed, press the Enter push-button to

accept the correction factor. Record the correction factor on the programming sheet for future reference.

Engine

Temperature

Sender

Resistance

Oil

Pressure

Sender

Resistance

5F

5C

Ohms

KPA

PSI

Ohms

392

200

20

1034

150

38

374

190

24

965

140

42

356

180

28

896

130

48

338

170

33

827

120

54

320

160

39

758

110

62

302

150

46

689

100

70

284

140

55

621

90

79

266

130

65

552

80

89

248

120

76

483

70

101

230

110

90

414

60

114

212

100

106

345

50

127

194

90

147

276

40

142

176

80

197

207

30

160

150

70

290

138

20

183

140

60

426

69

10

206

122

50

622

104

40

952

86

30

1486

68

20

2322

50

10

3644

32

0

6284

Note: Sender resistance data shown are for Oil Pressure Sender p/n-003654 (Thompson p/n), Manufacturer- Datcon, p/n

102227. Datcon Sender must be used with MEC software version 1.81 or greater (previous software versions cannot be

used).

Advertising