Chapter 2 – Installation and Wiring

2-7

Control Wiring

8

7

6

5

4

3

2

1

9

1

10

1

+ 10V Pot

Pot Wiper or
+10/–10V DC Input

Common
4–20mA Input

Reverse
Start

Common

Stop
Normally Closed

Relay Common

Normally Open

Signal

Specification

10 k

Potentiometer, 2 Watts

Controller Input Impedance = 100 k

Controller Input Impedance = 250

Contact closure input required to operate controller

Contact closure input

Contact closure input

Terminal

TB3

Customer-programmable relay outputs.
Resistive load 0.4A at 125V AC 2A at 30V DC.
Inductive load 0.2 A at 125V AC 1A at 30V DC.

FAULT

READY

Figure 2.3 – TB3 Control Wiring for Analog Signal Follower Model

FAULT

READY

8

7

6

5

4

3

2

1

9

1

10

1

SW1
SW2
Common
SW3

Reverse

Start
Common

Stop

Normally Closed

Relay Common

Normally Open

Signal

Specification

Contact closure input

Internal 12V supply.

Contact closure input

Contact closure input

Contact closure input required to operate controller

Contact closure input

Contact closure input

Terminal

TB3

Customer-programmable relay outputs.
Resistive load 0.4A at 125V AC 2A at 30V DC.
Inductive load 0.2 A at 125V AC 1A at 30V DC.

Shielded Wire

Figure 2.4 – TB3 Control Wiring for Preset Speed Model

Do not exceed control wiring length of 15 meters (50 feet)

.

Control signal cable length is highly dependent on

electrical environment and installation practices. To improve noise immunity the control terminal block common
must be connected to earth ground.

This diagram shows “three wire” control. Refer to the following page for diagrams of other control wiring methods.

Common

Common

Shielded Wire

= N.O. Maintained Contact

= N.C. Momentary Contact

= N.O. Momentary Contact

Common

= N.O. Maintained Contact

= N.C. Momentary Contact

= N.O. Momentary Contact

Common