Chapter 3

Program Keypad Module

3-1

Features

The program keypad module is located on the
front panel of the controller. It features the
following:

D five keys on the module for display or

programming controller parameters

D three keys for control inputs to the controller
D directional LEDs
D a 6 digit, seven segment LED display

Display Mode

The controller always powers up in the display
mode. While in this mode you may view all read
only controller parameters, but not modify them.

Program Mode

You enter the program mode by pressing the ESC
key. While in program mode, you can edit any
programmable controller parameters. Refer to
Chapter 5 for programming steps.

Figure 3.1 – Program Keypad Module Features

The

ESCape

key allows you to

toggle between the display mode

and program mode. When in

program mode, this key also

disables the editing of a parameter

value.

The

SELect

key is only used while in

program mode. It enables the editing of
a parameter value. When you press this
key the program mode indicator flashes.

Use the

up/down

arrow keys to scroll
through a list of
parameters, or increase
and decrease parameter
values. Press and hold
either key to increase
scrolling speed.

Pressing the

enter

key

while in programming
mode causes the current
value displayed to be
entered into memory. When
you press this key the
program mode indicator
remains on, but stops
flashing.

The

stop

key initiates the

motor to “Coast”, “Ramp” or
“DC Brake” to stop
depending on the setting of
P34 – [Stop Mode].

Pressing the

reverse

key causes the

motor to ramp down to 0 Hz and then

ramp up to its set speed in the opposite

direction.

The

clockwise LED

illuminates constantly when

the motor rotates in forward

direction.

The

counter clockwise LED

illuminates constantly when the

motor rotates in reverse direction.

When the

program mode

indicator

flashes, you can edit the

parameter value. When in display
mode, the program indicator does not
display.

These four digits
display the parameter
value or fault code
number.

These two digits display the active

parameter number for both display and

program parameters, which are

designated as P## throughout this

manual.

The

start

key initiates a

start command when the
controller is programmed
for local start/stop control
(when P46 – [Input Mode]
is set to “2”).

Indicates commanded direction. Actual motor rotation could be
different if motor leads are not connected properly. See
Chapter 4, Start-up for details on how to verify motor rotation.

When the motor is running, pressing this key causes the
(currently illuminated) LED to flash indicating motor rotation while

decelerating to zero. The opposite LED will illuminate indicating
the commanded direction.

Real time frequency adjustment can be achieved when using
P58 – [Internal Frequency].