Appendix B – CE Compliance

B-2

General Instructions for an EMC
Compliant Installation

Refer to Figure B.1.

Shielded Enclosure

D Typical NEMA or IEC metal enclosures are

adequate.

D The ground connection of the shielded

enclosure must be solidly connected to the PE
terminal of the controller. Good conductivity
must be assured – grounding must provide a
low impedance path to high frequency signals.

D All wiring, except input power leads, must use

shielded cable.

D Input power, output power and control wiring

inside the enclosure must be physically
separated.

D Input power, output power and control wiring

outside the enclosure must use separate
shielded cables, or separate conduit.

Cable Clamps

D Use suitable EMC-tested cable clamps only.

D The connection area must be 360 degrees

around the shielded cable.

D The cable clamps also provide strain-relief for

the cable.

D When using conduit, the contact point of

metal entry connections must be free of paint
or non-conductive surfaces and solidly
connected with good conductivity to the
enclosure.

Figure B.1 – Recommended Grounding Configuration

Control Wiring

Line Power

R (L1)

S (L2)

T (L3)

PE

AC

Input Line

Shielded Enclosure

Enclosure Ground Connection

U (T1)

Shielded Motor Cable

to TB3

Control

Cabinet *

to Motor

V (T2)

W (T3)

R (L1)

S (L2)

T (L3)

= EMC Tested Shielded Cable Clamp (or Metal Conduit)

*

TB3

Motor Wiring TB2

L2

L1

L3

BR

BR

1 2 3 4 5 6 7 8 9 10 11

T2

TI

T3

+

Ground Tab – PE

TB1

FAULT

READY

Line

Filter

DC

DC

W

V

U

+

T

S

R

When the control circuitry is located outside of the 160 enclosure.