Chapter 3 – Program Keypad Module

3-2

Removing Program Keypad Module

Dipswitch that changes P35 – [Base
Frequency]
from 50 to 60 Hertz
when program keypad module is not
installed.

Important: When a program keypad
module is installed, P35 – [Base
Frequency]
overrides this switch
setting. Once P35 – [Base Frequency]
is changed from its factory default
setting, the switch remains overridden
until all parameters are reset to their
factory default settings using
P56 – [Reset Defaults]

Program Keypad
Module

Figure 3.2 – Removing Program Keypad Module

Insert a small screw driver into
slot, pry back, and pivot module
out. Avoid bending or twisting the
contact pins located underneath
the center portion of the module.

ATTENTION: Ensure that you
disconnect line power and wait
one minute before installing or
removing the program keypad
module. Failure to do so may
result in personal injury or death.

Installing Program Keypad Module

Insert the module bottom end first and then press on the symbol at the top
of the module until the module is fully seated. The module is fully seated
when its face is flush with the edges of its surrounding case.

ATTENTION: This controller contains
ESD (Electrostatic Discharge) sensitive
parts and assemblies. Static control
precautions are required when installing,
testing, servicing or repairing this
assembly. Component damage may
result if ESD control procedures are not
followed. If you are not familiar with
static control procedures, reference A-B
Publication 8000-4.5.2, “Guarding
Against Electrostatic Damage” or any
other applicable ESD protection
handbook.