Appendix B –CE Compliance

B-3

Motor Cable

D The cable between the controller and motor

must be a 4-wire shielded cable (three phases
and ground). Refer to Figure B.2 and
Figure B.3.

D Do not exceed the maximum motor cable

length for the specific line filter module used.

D Inside the shielded enclosure, shielded motor

cable must be used as close to the controller’s
output terminals as possible. The shield must

be solidly connected to the PE terminal of the
controller.

D Where the shielded motor cable exits the

enclosure, an EMC-tested cable clamp, or
metal conduit must be used to solidly connect
the cable shield to the enclosure.

D The shield on the motor side must be solidly

connected to the motor housing with an
EMC-tested cable clamp, or conduit,
providing good conductivity from the cable
shield to the motor housing.

Figure B.2 – Motor Connections

Shielded Enclosure

U (T1)

V (T2)

W (T3)

= EMC Tested Shielded Cable Clamp (or Metal Conduit)

Motor Wiring TB2

L2

L1

L3

BR

BR

1 2 3 4 5 6 7 8 9 10 11

T2

TI

T3

+

Ground Tab – PE

FAULT

READY

4 Wire

Shielded Motor Cable

Ground to Motor Housing

+

T

S

R

DC

DC

W

V

U

Figure B.3 – Shielded Motor and Control Cable Example

Stranded Copper Wire

Plastic Insulation

Inner Plastic Sheath

Compact Screen of Galvanized (Tinned) Copper or Steel

Outer Plastic Jacket