Chapter 5 – Parameters and Programming

5-8

Program Group

P#

Parameter Description

Min/Max

Range

Units

Factory

Default

48

[Output Threshold]

Determines the on/off point for the TB3

output relay when [P47 – Output Configure] is set to 6, 7, and 8.

Settings

6

7

8

Ranges

0 to 240 Hz

0 to 180 %

0 to 815 Volts

0 to 815

Numeric

Value

0

49

[PWM Frequency]

Carrier frequency for the PWM output waveform.

The chart below provides derating guidelines based on the PWM freq. setting.

1

2

3

4

5

6

7

8

84

86

88

90

92

94

96

98

100

% Output Current (A)

Carrier Frequency, kHz

Important:

Ignoring derating guidelines can cause reduced controller perfor-

mance.

2.0 to 8.0

0.1 kHz

4.0 kHz

50

[Restart Tries]

Maximum number of times the controller will attempt to

reset a fault.

0 to 9

Numeric

Value

0

51

[Restart Time]

Time between restart attempts.

0.5 to 300

0.1 Seconds

10.0

Seconds

52

[DB Enable]

Enables/disables external dynamic braking.

Setting “0” = Disable. Settings 1 through 100 = % duty cycle braking.

Important:

The Rockwell Automation Bulletin 160 DB Resister package is rated

for 5% duty cycle. Use of this package above 5% should not be used and voids
the UL rating of this device. When setting this parameter to a value above 5%
duty cycle the resister must be sized to avoid overheating of the resister package.

Important:

This parameter cannot be programmed while the controller is

running.

0 to 100

Numeric

Value

0