Chapter 5 – Parameters and Programming

5-11

Program Group

P#

Parameter Description

Min/Max

Range

Units

Factory

Default

61

[Preset Frequency 0]

The programmed value sets the frequency that

the controller outputs when selected.

0 to 240

0.1 Hz

3 Hz

62

[Preset Frequency 1]

The programmed value sets the frequency that

the controller outputs when selected

0 to 240

0.1 Hz

20 Hz

63

[Preset Frequency 2]

The programmed value sets the frequency that

the controller outputs when selected.

0 to 240

0.1 Hz

30 Hz

64

[Preset Frequency 3]

The programmed value sets the frequency that

the controller outputs when selected.

0 to 240

0.1 Hz

40 Hz

65

[Preset Frequency 4]

The programmed value sets the frequency that

the controller outputs when selected.

0 to 240

0.1 Hz

45Hz

66

[Preset Frequency 5]

The programmed value sets the frequency that

the controller outputs when selected.

0 to 240

0.1 Hz

50 Hz

67

[Preset Frequency 6]

The programmed value sets the frequency that

the controller outputs when selected.

0 to 240

0.1 Hz

55 Hz

68

[Preset Frequency 7]

The programmed value sets the frequency that

the controller outputs when selected.

0 to 240

0.1 Hz

60 Hz

69

[Accel Time 2]

Time for the controller to ramp from 0.0 Hz. to P33 –

[Maximum Frequency]. The rate is linear for any increase in command frequency
unless P53 – [S-Curve] is set to a value other than “0”. Setting this to 0.0 sec.
gives 0.1 sec acceleration with the initial current limit turned off. This allows
quicker acceleration times for low inertia systems. For medium to high inertia
systems, the minimum value should be 0.1 sec.

0.0 to 600

0.1 Sec.

20.0 Sec.

70

[Decel Time 2]

Time for the controller to ramp from P33 – [Maximum

Frequency] to 0.0 Hz. The rate is linear for any decrease in command frequency
unless P53 – [S-Curve] is set to a value other than “0”.

0.1 to 600

0.1 Sec.

20.0 Sec.

=

This parameter applies only to the Preset Speed model

Preset Accel/Decel Chart For Preset Speed Model Only

TB3-4
(SW3)

TB3-2
(SW2)

TB3-1
(SW1)

Preset

Accel

Decel

0

0

0

Preset 0

0

0

1

Preset 1

P

ccel T me

P

Decel T me

0

1

0

Preset 2

P30 – [Accel Time 1]

P31 – [Decel Time 1]

0

1

1

Preset 3

1

0

0

Preset 4

1

0

1

Preset 5

P

ccel T me

P7

Decel T me

1

1

0

Preset 6

P69 – [Accel Time 2]

P70 – [Decel Time 2]

1

1

1

Preset 7

Refer to Figure 2.4 for the Preset Speed model control wiring diagram.

When using P46 – [Input Mode] setting “4” the Accel and Decel times are selected by providing an input to TB3-8. See page 2-9 for additional
information.