Chapter 5 – Parameters and Programming

5-3

Display Group

P#

Parameter Description

Min/Max

Range

Units

12

[Input Status]

Displays the open (0) and closed (1) state of the

inputs to TB3 in binary coded format as follows:

Bit 3

Bit 2

Bit 1

Bit 0

Input
Mode 0
(3-Wire)

Input
Mode 1
(2-Wire)

Input Mode 3
(Momentary
Run FWD/
Run REV)

Input
Mode 4
(Accel/
Decel)

Input
Mode 5
(Enable)

Input Mode 6
(Local/
Remote)

Bit 0
TB3-5

Reverse

Run

Reverse

N/A

Run

Reverse

Run

Reverse

Run

Reverse

Run

Reverse

Stop

Start

Stop

Run

Forward

N/A

Stop

Run

Forward

Stop

0=Accel 2/

Decel 2

1=Accel 1/

Decel 1

Run

Forward

0=Drive

Disable

1=Drive

Enable

Run

Forward

0=Local (TB3)

Control

1=Remote

Control

Bit 1
TB3-8

Bit 2
TB3-6

Bit 3
Polarity

Input
Mode 2
(Keypad)

Run

Forward

0 = Positive Analog Input
1 = Negative Analog Input

0000 to 1111

Binary Number

13

[Power Factor Angle]

Displays the angle in electrical degrees between motor

voltage and motor current.

0.0 to 180.0

0.1 degrees

БББ

Б

Б

Б

БББ

14

[Memory Probe Display]

Used by Rockwell Automation field service

personnel.

ББББББ

Б

ББББ

Б

ББББББ

Numeric Value

ББББ

Б

ББ

Б

ББББ

Numeric Value

15

[Preset Status]

Displays the open (0) and closed (1) state of Terminal Block Three

(TB3) inputs SW1, SW2, and SW3 in binary coded format. This parameter applies to the
Preset Speed model only.

Bit 3

Bit 2

Bit 1

Bit 0

Not Used

SW2

SW3

SW1

0000 to 0111

Binary Number

ЙЙЙ

Й

Й

Й

Й

Й

Й

Й

Й

Й

Й

Й

Й

ЙЙЙ

16

БББББББББББББББББББ

Б

БББББББББББББББББ

Б

Б

БББББББББББББББББ

Б

Б

БББББББББББББББББ

Б

Б

БББББББББББББББББ

Б

БББББББББББББББББББ

[Analog Input]

Displays the analog input as a percent of full scale. Used in setting

P60 – [Zero Offset], P75 – [Analog Input Minimum], and P76 – [Analog Input
Maximum].

Important:

On initial set up of the controller, apply a 0V or 4mA analog command to the

controller. Once applied, if the value of this parameter displays something other than zero,
program that value into P60 – [Zero Offset]. Important: The value of the [Zero Offset] will
be subtracted from the value of this parameter.

ББББББ

Б

ББББ

Б

Б

ББББ

Б

Б

ББББ

Б

Б

ББББ

Б

ББББББ

–150 to +150.0

ББББ

Б

ББ

Б

Б

ББ

Б

Б

ББ

Б

Б

ББ

Б

ББББ

0.1%

=

This parameter applies only to the Preset Speed model.

ЙЙЙ

ЙЙЙ

=

This parameter applies only to the Analog Signal Follower model.