Chapter 5 – Parameters and Programming

5-5

Program Group

P#

Parameter Description

Min/Max

Range

Units

Factory

Default

37

[Maximum Voltage]

Sets the highest voltage that the controller will

output.
P37 – [Maximum Voltage] must be greater than or equal to P36 – [Base Voltage].

20 to 510 for

460V units and

20 to 255 for

230V units

1 Volt

460 Volts for

460V units

and 230 for

230V units

38

[Boost Select]

Sets the boost voltage and redefines the Volts per Hz

curve.

[Base Frequency], %

[Base

V

oltage], % 50

100

1/2
Base
Volts

50

100

1/2 Base

Freq.

9
10
11
12

0

1

8

y

b

See Settings 1

through 8 below

Setting

Boost Voltage % of [Base Voltage]

1

2.5

2

5.0

3

7.5

4

10.0

5

12.5

6

15.0

7

17.5

8

20.0

0

0

Setting Fan/Pump Curves

Break Point Voltages

in % of [Base Voltage].

9

45.0

10

40.0

11

35.0

12

30.0

0 to 12

Numeric

Value

2

39

[Skip Frequency]

Works in conjunction with P40 – [Skip

Frequency Band] creating a range of frequencies at which the controller will
not operate continuously.

'

b

y

Two times

P40–[Skip Freq Band]

Setting

'

Skip

Frequency

Setting

Frequency

Time

Controller Output
Frequency

a

Command

Frequency

0 to 240

1 Hz

240 Hz

40

[Skip Frequency Band]

Determines the band around the P39 –

[Skip Frequency] parameter. The actual band width will be 2 times [Skip
Frequency Band
] – 1/2 the band above and 1/2 the band below. A value of zero
will disable the skip frequency.

0 to 30

1 Hz

0 Hz