Chapter 5 – Parameters and Programming

5-2

Display Group Parameters

This group of parameters consists of commonly viewed controller operating conditions such as controller
output frequency, output voltage, output current and frequency command. All parameters in this group
are read only.

Important: The last user selected Display Group parameter will be saved on power down.

Display Group

P#

Parameter Description

Min/Max

Range

Units

01

[Output Frequency]

Displays the output frequency at TB2 terminals T1, T2 and

T3 (U, V and W).

0 to 240

0.1 Hz

02

[Output Voltage]

Displays the output voltage present at TB2 terminals T1, T2 and

T3 (U, V and W).

0 to [Max Voltage]

1 Volt

03

[Output Current]

Displays the output current present at TB2 terminals T1, T2 and

T3 (U, V and W).

0 to 2 Times

Controller Rated

Output Current

0.01Amps

04

[Output Power]

Displays the output power present at TB2 terminals T1, T2 and T3

(U, V and W).

0 to 2 Times Rated

Controller Output

Power

0.01 kW

05

[Bus Voltage]

Displays the DC Bus Voltage level.

0 to 400 – [230V]

0 to 800 – [460V]

1 Volt

06

[Frequency Command]

Displays the frequency that the controller is

commanded to output. This command may come from any of the frequency sources
selected by

P59 – [Frequency Select]

or from a currently selected preset frequency.

0 to 240

0.1 Hz

07

[Last Fault]

Displays the coded last fault number. If a fault is currently active (has not

been cleared) the display will flash. See Chapter 6 for fault code descriptions.

0 to 49

Numeric Value

08

[Heatsink Temperature]

Displays the temperature of the controller heatsink.

0 to 150

1 Degree C

09

[Controller Status]

Displays the status of the controller in a binary

coded format.

Bit 3

Bit 2

Bit 1

Bit 0

Running

Accel

Forward

Decel

Important:

A “0” = inactive

and a “1” = active.

0000 to 1011

Binary Number

10

[Controller Type]

Used by Rockwell Automation field service personnel.

Numeric Value

Numeric Value

11

[Control Version]

Displays version of controller firmware. Used by Rockwell

Automation field service personnel.

Fixed Value

Numeric Value