Chapter 5 – Parameters and Programming

5-7

Program Group

P#

Parameter Description

Min/Max

Range

Units

Factory

Default

46

[Input Mode]

Configures the TB3 control inputs for various “3 wire” or “2

wire run-fwd/run-rev control” schemes. Also enables/disables the program keypad
module input control.

Important:

This parameter cannot be programmed while

the controller is running. Also, power must be cycled or P56 – [Reset Func-
tion] must be set to “2” for the change to take effect.

Settings:

0 = “3 wire” control
1 = “2 wire” control
2 = Program Keypad Module control
3 = Momentary ‘‘Run Forward/ Run Reverse” control

4 = 2 wire “Accel/Decel” control
5 = 2 wire “Enable” control
6 = 2 wire “Local/Remote” control

See Chapter 2 for wiring diagrams and description of settings.

0 to 6

Numeric

Value

0

47

[Output Configure]

Configures the TB3 relay output functionality.

Settings

0 = Controller

Ready/Faulted

1 = At Frequency

2 = Controller Running

3 = Reverse

4 = Motor Overload

5 = Ramp Regulated

7= Above Current

6 = Above Frequency

Output changes state when...

8 = Above DC Bus

Voltage

energized and returns to shelf state when
power is removed or when a fault occurs.

the controller reaches commanded frequency.

the controller is running.

the controller is commanded to run in the reverse
direction.

when a motor overload condition exists.

the ramp regulator is modifying the
programmed accel/decel times to avoid an
overcurrent or overvoltage fault from occurring.

the controller exceeds the frequency value
set in P48 – [Output Threshold].

the controller exceeds the value set in P48 –
[Output Threshold]
. Important: Value for
P48 – [Output Threshold] must be entered in
% of controller rated output current.

the controller exceeds the DC bus voltage value set
in P48 – [Output Threshold].

9 = Retries Exhausted

the number of retries for P50 – [Restart Tries] is
exceeded.

0 to 9

Numeric

Value

0