Chapter 2 – Installation and Wiring

2-9

Control Wiring (continued)

Figure 2.8 – TB3 Two Wire “Accel/Decel” control

(Setting 4)

8

7

6

5

Run Reverse
Run Forward

Common
Accel/decel
select

Signal

Specification

Contact Closure Input

Used to select Accel/Decel.

Terminal

TB3

Shielded Wire

Contact Closure Input

Contact Closure Input

Common

Refer to Figure 2.11.

Figure 2.9 – TB3 Two Wire “Enable” control

(Setting 5)

Specification

8

7

6

5

Run Reverse

Run Forward

Enable

Common

Signal

Contact Closure Input required
to operate controller

Common

Terminal

TB3

Shielded Wire

Contact Closure Input

Contact Closure Input

Refer to Figure 2.11.

Figure 2.10 – TB3 Two Wire “Local/Remote” control

(Setting 6)

Specification

8

7

6

5

Run Reverse
Run Forward

Local/
Remote

Common

Signal

Contact Closure Input

Used to select local (TB3)
Control.

Common

Contact Closure Input

Terminal

TB3

Shielded Wire

Contact Closure Input

Refer to Figure 2.11.

Figure 2.11

Input Mode

Setting

TB3-8

Open

TB3-8

Closed

4

Accel 2

Decel 2

Accel 1

Decel 1

5

Controller

Disabled

Controller

Enabled

6

Local (TB3)

Control

Remote

Control

The “Run” input must be a maintained input. After a stop
command, either a “Run Forward” or “Run Reverse” input must
be toggled to start the controller.

When this input is in an open state, P69 – [Accel Time 2] and
P70 – [Decel Time 2] are active.

When this input in in an open state, all power is removed from
the motor and it will “coast to rest”.

When this input is in an open state the Frequency source is
always from the terminal block regardless of the setting of
P59 – [Frequency Select].

Important: In modes 4 through 6, Terminal
TB3-8 is also used to clear faults. See Figure 2.12
for details.

Important: The system programmer is
responsible for returning terminal TB3-8 to its
original state if necessary.

Figure 2.12

TB3-8
CLOSED

TB3-8
OPEN

Fault
occurs

Fault
clears

Fault
clears

Fault
occurs

Advertising