Function Block Library
4–45
1336 FORCE — 5.9 August 1995
PARAMETERS
DATA TYPE
LINKABLE
DEFAULT VALUE
RANGE
Lim In
Signed Integer
Yes
0
±
32767
Lim Set
Logic Input
Yes
0
True/False
Lim Data
Signed Integer
Yes
0
±
32767
Lim Rate
Unsigned Integer
No
0
0 to 65535
Lim @ Lim
Logic Output
No
—
True/False
Lim Out
Signed Integer
No
—
±
32767
Lim @Lim = True
Time
Example 1
+ 32767
0
– 32767
Lim @Lim = False
When Lim Rate = 65535, t1 = 1 sec
When Lim Rate = 32767, t1 = 2 sec
Lim In
Lim Out
t1
RATE LIMITER