Delay – Rockwell Automation 1336T Function Block Prog. Manual, Series A/B User Manual
Page 74
Function Block Library
4–12
1336 FORCE — 5.9 August 1995
PARAMETERS
DATA TYPE
LINKABLE
DEFAULT VALUE
RANGE
Input
Logic Input
Yes
0
True/False
Enable
Logic Input
Yes
0
True/False
On (ms)
Unsigned Integer
No
0
0 to 65535
Off ms.
Unsigned Integer
No
0
0 to 65535
Out
Logic Output
No
—
True/False
Out Not
Logic Output
No
—
True/False
INPUT
t1
Example
ENABLE = TRUE
ON MS
= 40mS = t1
OFF MS
= 20mS = t2
mS
OUT
OUT NOT
0
20
40
60
80
100
120
140
t2
Important:
The on and off timers operate independently.
Once the on delay timer (t1) is initiated, subsequent rising edges are
ignored.
Once the off delay timer (t2) is initiated, subsequent falling edges are
ignored.
1. The on duration time of input pulses should be checked when the ON MS
> OFF MS.
2. The off duration time of input pulses should be checked when the OFF
MS > ON MS.
DELAY
(continued)