Function Block Library

4–12

1336 FORCE — 5.9 August 1995

PARAMETERS

DATA TYPE

LINKABLE

DEFAULT VALUE

RANGE

Input

Logic Input

Yes

0

True/False

Enable

Logic Input

Yes

0

True/False

On (ms)

Unsigned Integer

No

0

0 to 65535

Off ms.

Unsigned Integer

No

0

0 to 65535

Out

Logic Output

No

True/False

Out Not

Logic Output

No

True/False

INPUT

t1

Example

ENABLE = TRUE
ON MS

= 40mS = t1

OFF MS

= 20mS = t2

mS

OUT

OUT NOT

0

20

40

60

80

100

120

140

t2

Important:

The on and off timers operate independently.

Once the on delay timer (t1) is initiated, subsequent rising edges are
ignored.

Once the off delay timer (t2) is initiated, subsequent falling edges are
ignored.

1. The on duration time of input pulses should be checked when the ON MS

> OFF MS.

2. The off duration time of input pulses should be checked when the OFF

MS > ON MS.

DELAY

(continued)