Function Block Library

4–54

1336 FORCE — 5.9 August 1995

Example 1 — Horizontal Scale = 1 S/Division

A UP/DWN CNTR Output

+ 32767

"

– 32767

"

0

"

A–––––––––––––––––––––––– 7.4 Seconds ––––––––––––––––––––––––"

Preset = + 32767
Select = 0
UD1 = 2048
Time = 240 mS
Inc = 1
Dec = 0
Min = – 32767
Max = + 32767

The number of iterations required to decrement the output from it’s Preset value of + 32767
to the Min value of – 32767 would be:

Total Iterations = Range

÷

Increment = 65534

÷

2048 = 31.99

31.

The time it takes to traverse from a Max setting of + 32767 to – 32767 would be:

Total Time = Total Iterations

÷

Time Input = 31

×

240 mS = 7.44 S or approximately 7.4 S.

Example 2 — Horizontal Scale = 1 S/Division

UP/DWN CNTR Output

"

+ 32767

"

– 32767

"

0

"

A–––––––––––––––––––––––– 7.4 Seconds ––––––––––––––––––––––––"

Preset = – 32767
Select = 0
UD1 = 2048
Time = 240 mS
Inc = 0
Dec = 1
Min = – 32767
Max = + 32767

Example 2 is similar to Example 1 except the UP/DWN CNTR must count up from a Preset
value of – 32767.

UP/DWN CNTR

(continued)