5–19

Block Transfer Services

1336 FORCE — 5.9 August 1995

The PLC Communication Board sends this message to activate the
function block BRAM function that is detailed in the message
request.

PLC Block Transfer Instruction Data

BTW Instruction Length:

4 Words

BTR Instruction Length:

4 Words

PLC Decimal Value

-28926

Not used

0

BRAM Command

BRAM Store
BRAM Recall
BRAM Initialize

BRAM Command

Value

0
1
2
3

Message Structure

PLC Request –– Block Transfer Write

Data Word 4

Header Word 1

Header Word 2

Header Word 3

Header

Word 1

PLC Decimal Value

3842 –– Message OK

0

–28926 –– Message Error

Header

Word 2

Header

Word 3

0

0

Drive Response –– Block Transfer Read

BRAM Command

Data

Word 4

Message Operation

A BRAM Store saves the function block program that is currently in
RAM to the function block BRAM/EEPROM.

A BRAM Recall copies the function block program that is stored in
BRAM to RAM. The drive executes the program stored in RAM.

A BRAM Initialize erases the function block program stored in
RAM and all associated function block links including links to linear
drive parameters. A BRAM Initialize function does not actually
clear out the BRAM itself; it only clears the function block
application out of the working RAM area.

Refer to Chapter 3 for a more detailed description of BRAM
functionality.

Application Control
Commands:

BRAM Functions
Store, Recall, and Initialize

"