1–6

Getting Started

1336 FORCE — 5.9 August 1995

You can now link the Set Reset Flip Flop inputs to the outputs of the
Limit function block entered in

Step 1

.

5. Link the Set Reset FF’s set input (node 0), to the maximum limit

flag of the Limit function block (node 3).

Click on the

Link To

field for

Node 0

and enter

1:3.

Press enter to save the value as shown below.

6. Link the Set Reset FF’s reset input (node 1), to the minimum limit

flag of the Limit function block (node 4).

Click on the

Link To

field for

Node 1

and enter

1:4

.

Press enter to save the value as shown above.

With the Set Reset FF function block and links added, the function
block diagram now appears like this.

Input 1 1:0

Max Val (32765) 1:1

LIMIT

ID # 1

@ Max Lim 1:3

@ Min Lim 1:4

Output 1:5

Min Val (–32765) 1:2

Set Reset FF

ID # 2

Set 2:0

Reset 2:1

Out1 2:2

Out2 2:3