Rockwell Automation 1336T Function Block Prog. Manual, Series A/B User Manual
Page 70
Advertising
Function Block Library
4–8
1336 FORCE — 5.9 August 1995
PARAMETERS
DATA TYPE
LINKABLE
DEFAULT VALUE
RANGE
In1
Signed Integer
Yes
0
±
32767
Pre
Signed Integer
No
0
±
32767
Hyst
Unsigned Integer
No
0
0 to + 32767
EQ
Logic Output
No
—
True/False
LT
Logic Output
No
—
True/False
GT
Logic Output
No
—
True/False
EXAMPLES
EXAMPLE 1
EXAMPLE 2
In1
8
15
Pre
10
10
Hyst
3
3
EQ
True
False
LT
True
False
GT
False
True
COMPHYST
(continued)
Advertising