Sawtooth application operation – Rockwell Automation 1336T Function Block Prog. Manual, Series A/B User Manual

Page 14

Advertising
background image

1–2

Getting Started

1336 FORCE — 5.9 August 1995

The output from the RATE LIMITER function block will be a sawtooth
signal. The value of the RATE LIMITER output will ramp up to the
value specified by the MULTIPLEXER input #1 (+ 32767). When the
RATE LIMITER output reaches the maximum value specified by the
LIMIT block t1 (+32765), the max limit flag will set the SR FLIP
FLOP
output, which in turn selects the MULTIPLEXER input #2. The
RATE LIMITER output will then ramp down to this new value of
– 32767.

Max Value

Min Value

Max Value

Min Value

Out 1

RATE LIMIT

LIM

MULTIPLEXER Out

Lim In

RATE LIMITER

t1

"

Input

LIMIT

Set

SR FLIP FLOP INPUTS

Reset

A

B

C

At2

At2

When the RATE LIMITER output reaches the minimum value specified
by the LIMIT block (– 32765), the min limit flag will clear the SR
FLIP FLOP
output (t2), which in turn selects the MULTIPLEXER input
#1. The RATE LIMITER output will continue to ramp up and down
between the LIMIT block minimum and maximum values.

Sawtooth Application
Operation

Advertising